Disjuntor Caixa Moldada NF-S Mitsubishi NF50-SVFU2P10AY 2P 10A 14kA (UL) com Auxiliar e Bornes Verticais

Consulte as Condições de Fornecimento

Disjuntor Caixa Moldada Mitsubishi NF50-SVFU2P10AY 2P 10A 14kA

SKU: NF50-SVFU2P10AY Categoria: Marca:

Moulded Case Circuit Breaker (MCCB) with pre-installed auxiliary sw. + vertical lead-wire term. block – Mitsubishi (UL 489 Listed MCCBs – NF-S (standard class)) – 2-poles (2P) – Rated current 10A – Short circuit breaking capacity (Icu) 10kA (400Vac; IEC60947) – Short circuit current rating 14kA (240Vac; UL489) – Thermal-Magnetic (fixed) trip unit – Front lugs or bars connection connection

Especificações

Parâmetro Valor
Primary brand Mitsubishi
Main function Moulded Case Circuit Breaker (MCCB)
Product series / family name UL 489 Listed MCCBs
Sub-range name NF-S (standard class)
Functions Moulded / Molded Case Circuit Breaker (MCCB)
Design pre-installed auxiliary sw. vertical lead-wire term. block
Poles 2-poles (2P)
Rated current 10A
Trip current rating 10 AT
Frame current rating 50 AF
Rated voltage (AC) 240Vac (UL 489)
Rated impulse voltage (Uimp) 6 kV
Rated insulation voltage (Ui) 440 V
Connection type Front lugs or bars connection
Short circuit breaking rating 14kA (240Vac; UL489)
Ultimate short circuit current breaking capacity (Icu) 15kA (230Vac; IEC60947) 10kA (380Vac; IEC60947) 10kA (400Vac; IEC60947) 10kA (415Vac; IEC60947) 7.5kA (440Vac; IEC60947)
Service short circuit current breaking capacity (Ics) 8kA (230Vac) 5kA (380Vac) 5kA (400Vac) 5kA (415Vac) 4kA (440Vac)
Service short circuit current breaking capacity as a percentage of Icu (Ics%) (400Vac) 50 %
Trip unit type Thermal-Magnetic (fixed)
Protection functions Thermal protection (Overload) Magnetic protection (Short-circuit)
Protection settings Thermal protection (Overload) — tripping threshold fixed at 10A
Mounting mode Surface mounting (or DIN rail with optional adapter)
Dimensions W36mm x H120mm x D90mm
Utilisation category A
Manufacturer product status Commercialized
Equivalent to NF50SVFU2P10AY
Compliant with standard(s) IEC 60947-2 EN 60947-2 UL 489 CSA C22.2 No.5-02 TUV approval CE marking
Benefits The all-new “World Super V Series (WS-V Series)” built with a new breaking technology is designed to respond to the individual market needs of the receiving and distribution and machineries. This series is the result of revolutionary evolution Equipped with a new cutoff technology to enhance interrupting performance Compatible with the latest standards of various countries to deliver optimal performance according to individual needs.
Degree of pollution 3

Documentos