Disjuntor Caixa Moldada (MCCB) com DR Mitsubishi WS-V NV-S 3P 40A 30mA 30kA NV125-SV3P40A30

Consulte as Condições de Fornecimento

Principais recursos

  • Disjuntor de caixa moldada (MCCB) com proteção contra fuga de terra
  • Tipo de alta velocidade
  • 3

SKU: NV125-SV3P40A30 Categoria: Marca:

Documentos

A série WS-V da Mitsubishi Electric representa uma evolução em tecnologia de disjuntores, oferecendo desempenho aprimorado e conformidade com os padrões internacionais mais recentes.

Para mais informações ou para discutir suas necessidades específicas, entre em contato conosco.

Entre em contato

Especificações

Parâmetro Valor
Primary brand Mitsubishi
Main function Moulded Case Circuit Breaker (MCCB) with embedded earth leakage protection / ELCB
Product series / family name WS-V series
Sub-range name NV-S (standard class) harmonic surge ready
Functions Moulded Case Circuit Breaker (MCCB) with embedded earth leakage protection / Earth Leakage Circuit Breaker (ELCB)
Design high-speed type
Poles 3-poles (3P)
Rated current 40A
Trip current rating 40 AT
Frame current rating 100 AF
Residual current sensitivity 30mA
Rated impulse voltage (Uimp) 6 kV
Connection type Front lugs or bars connection
Ultimate short circuit current breaking capacity (Icu) 50kA (100Vac; IEC60947) 50kA (200Vac; IEC60947) 50kA (230Vac; IEC60947) 30kA (400Vac; IEC60947) 30kA (415Vac; IEC60947) 25kA (440Vac; IEC60947)
Service short circuit current breaking capacity (Ics) 50kA (100Vac) 50kA (200Vac) 50kA (230Vac) 30kA (400Vac) 30kA (415Vac) 25kA (440Vac)
Service short circuit current breaking capacity as a percentage of Icu (Ics%) (400Vac) 100 %
Trip unit type Thermal-Magnetic (fixed)
Protection functions Thermal protection (Overload) Magnetic protection (Short-circuit) Earth leakage protection
Protection settings Thermal protection (Overload) — tripping threshold fixed at 40A
Dimensions W90mm x H130mm x D90mm
Electrical durability (with load) 10000 operations
Mechanical durability (at no load) 25000 operations
Utilisation category A
Manufacturer product status Commercialized
Equivalent to NV125SV3P40A30
Rated Voltage (AC) – Phase-to-phase 100-440 V
Compliant with standard(s) IEC 60947-2 EN 60947-2 CE marking
Benefits The all-new “World Super V Series (WS-V Series)” built with a new breaking technology is designed to respond to the individual market needs of the receiving and distribution and machineries. This series is the result of revolutionary evolution Equipped with a new cutoff technology to enhance interrupting performance Compatible with the latest standards of various countries to deliver optimal performance according to individual needs.
Degree of pollution 2
Marca

Mitsubishi Electric